After Calculate the table under the drawing lists every room with its loads, one row per room and a SUBTOTAL row per floor; the header above it starts as "No results — pick a config and press Calculate" and then reads "Results — <config> (<station> (<distance>), <method>)" once a run finishes. The results pane has tabs: Cooling Load (this table), Heating Load (only when the configuration calculates heating loads) and Coincident peak. The grand TOTAL row across every room of the cooling table is a feature of Exporting results only, never shown on the Cooling Load tab.

Click a column heading on any of the three tabs to sort by it; click it again to reverse. Rooms sort within their own floor, so each SUBTOTAL row stays under its floor's rooms, and the zone and TOTAL rows stay at the bottom. On Coincident peak the Whole building row stays on top. Empty cells go last either way. The sort lasts until you close the app, and exports always keep the original order.
The Floor and Zone filters sit in one row above the tabs and act on both the Cooling Load and Heating Load tables. On the Coincident peak tab they are greyed out: that tab is never filtered. The gear at the end of the row chooses columns for the Cooling Load tab only, so it is greyed on the other tabs.
| Field | What it does | Default | Read more |
|---|---|---|---|
| Floor | Shows only rooms on the chosen floor. | All floors | Floor |
| Zone | Shows only rooms in the chosen zone. | All zones | Zone |
Keeps only the rooms on the chosen floor and recomputes the SUBTOTAL rows for what remains. All floors (the default) brings every floor back.
Keeps only rooms assigned to the chosen zone. All zones (the default) brings every room back; filtering never changes a stored result, only what the table currently shows.

| Field | What it does | Default | Read more |
|---|---|---|---|
| Floor | Names the floor the room sits on. | — | Floor |
| Room Name | Names the room. | — | Room Name |
| Room No. | Shows the number typed for the room. | — | Room No. |
| Zone | Names the zone the room belongs to, on the zone's color. | — | Zone |
| Schedule | Names the hourly profile the room follows, or Always 100%. | — | Schedule |
| Width | The room's resolved width. | Length | Width |
| Depth | The room's resolved depth. | Length | Depth |
| Area | The room's floor area. | Area | Area |
| Partition area | Interior wall area charged as partition, after air-conditioned neighbours are taken off. | Area | Partition area |
| Occupancy | The room's design number of people. | — | Occupancy |
| Lighting | The room's lighting at full use, before its schedule. | Heat load | Lighting |
| Equipment | The room's equipment at full use, before its schedule. | Heat load | Equipment |
| Room Sens | Dry heat the room itself gains. | Heat load | Room Sens |
| Room Lat | Moisture load the room itself gains. | Heat load | Room Lat |
| OA Sens | Dry-heat load of the room's fresh air. | Heat load | OA Sens |
| OA Lat | Moisture load of the room's fresh air. | Heat load | OA Lat |
| ERSH | Room dry heat plus the bypassed fresh-air share. | Heat load | ERSH |
| ERLH | Room moisture load plus the bypassed fresh-air share. | Heat load | ERLH |
| Grand Total | Everything the coil has to remove. | Heat load | Grand Total |
| Capacity | The cooling capacity selected for the room. | Cooling capacity | Capacity |
| Intensity | Grand Total per unit floor area. | Load intensity | Intensity |
| ESHF | The dry-heat share of the effective room load. | — | ESHF |
| ADP | The coil surface temperature the search settled on. | Temperature | ADP |
| Rise | How much colder than the room the supply air is. | Temperature difference | Rise |
| Supply air | The supply-air flow the room needs. | Airflow | Supply air |
| Supply | Temperature of the air delivered to the room. | Temperature | Supply |
| Entering | Mixed-air temperature entering the coil. | Temperature | Entering |
| Leaving | Air temperature leaving the coil. | Temperature | Leaving |
| Flag | Any flag raised on the room. | — | Flag |
| Sizing Case | Names the design day that governed the room. | — | Sizing Case |
| Peak DB Total | The room's total under the hottest-air design day. | Heat load | Peak DB Total |
| Peak WB Total | The room's total under the most-humid design day. | Heat load | Peak WB Total |
Each row's Default here is the unit kind its column follows, in brackets in the column header, which changes with the Units setting; "—" marks a column that carries no unit.
The calculation itself always works in SI: watts for heat, degrees Celsius for temperatures, kelvin for temperature differences, square metres for areas, cubic metres per second for air, and kilograms of water per kilogram of dry air for moisture. Choosing IP changes the display only, so every formula below is written in SI.
Symbols used below.
How the columns chain together. Room Sens and Room Lat are what the room itself gains. OA Sens and OA Lat are what the fresh air brings in, and the coil bypass factor splits that between the room side (ERSH, ERLH) and the coil side. ESHF, Grand Total, ADP, Rise and the four air temperatures all follow from those. The same chain is set out step by step under From room load to coil duty, and every number in it for one room can be read in Explain.
Which run a row shows. With "Peak dry-bulb & wet-bulb" each room is calculated twice, once against the hottest day and once against the most humid day, and the row shows whichever run produced the larger Grand Total — every column in that row comes from that one run. The losing run is not shown; Sizing Case names the winner, and Peak DB Total and Peak WB Total carry both runs' Grand Totals regardless of which one won. See Calculation method.
The floor the room sits on, matching the floor tab it was drawn on. There is no formula: the name is stamped onto the result as the floor is calculated.
Floors are calculated from the lowest level upwards, and each floor's block of rooms ends with a SUBTOTAL row that repeats the floor name in this column. Whether a floor gets a roof load or a ground-slab load is decided by Top floor (roof load) and Ground floor (floor load), so two rooms of the same size on different floors can differ by a large amount.
The room's name, exactly as it appears in the Rooms list and on the drawing. No formula: it is copied from the room.
The name does not decide NON-AC itself: the room's Air-conditioned setting does. That setting is filled from the name until you set it by hand. On a floor's summary line this column reads SUBTOTAL in place of a room name. See Name.
The number typed for the room, or blank when none was typed. No formula, and it never affects the calculation.
Blank on SUBTOTAL rows. See Room number.
The name of the zone the room belongs to, written on the zone's color — the cell's background is the color the zone has on the canvas, and the name is set in black or white, whichever reads on it. No formula: it is read from the zone assigned to the room. In Excel the cell is filled with the zone's color too.
Blank on SUBTOTAL rows. See Putting rooms in a zone.
The name of the schedule assigned to the room, or Always 100% when none is. It prints the short name, family and space type, for example Hospitality · Guest room, weekday; Explain and the exports print the full name with its source in front. No formula: it is read from the room. A room at Always 100% counts its people, lighting, equipment and fresh air at full value in every hour.
Blank on SUBTOTAL rows.
The room's width in the Length unit, as already resolved from the drawing. No formula of its own.
If the room's label on the drawing stated a size, that stated figure is used; otherwise it is the shorter side of the smallest rectangle that can be drawn around the room's wall boundary at any angle. Nothing in the load calculation uses it — every area in the formulas below comes from Area or from the walls themselves. Shown to two decimals, and blank on SUBTOTAL rows. Off by default; add it with Choose Columns. See Area, perimeter and glass.
The room's depth in the Length unit, resolved the same way as Width. No formula of its own.
A size stated on the room's label wins again; otherwise it is the longer side of that same smallest rectangle around the wall boundary. Like Width it is reported only, never calculated with. Shown to two decimals, and blank on SUBTOTAL rows. Off by default; add it with Choose Columns. See Area, perimeter and glass.
The room's floor area, in the Area unit. No formula: it is the area enclosed by the room boundary.
It is used in five places in the calculation — roof and ground-slab conduction, the lighting and equipment gains, the per-area part of the fresh-air quantity, the occupant count itself for a room whose occupants are estimated from density, and as the divisor in Intensity. Summed across the floor's rooms on SUBTOTAL rows, and shown to two decimals. See Area, perimeter and glass.
The interior wall area the run charged as partition, in the Area unit: each interior wall's charged length times the room's ceiling height. A stretch of wall that faces an air-conditioned room carries nothing and is left out; a stretch facing a non-air-conditioned room, or nothing drawn, is counted. A wall whose Other side was set by hand counts all or none of its interior face. Summed across the floor on SUBTOTAL rows. Off by default; add it with Choose Columns.
The room's design number of people: its floor area divided by the space type's floor area per person, or the number typed for the room. Summed across the floor on SUBTOTAL rows.
The room's lighting, in the Heat load unit, at full use: its lighting density times its floor area, before the schedule takes any of it off. Summed across the floor on SUBTOTAL rows.
The room's equipment, in the Heat load unit, at full use, worked out the same way as Lighting from the equipment density. Summed across the floor on SUBTOTAL rows.
Room sensible heat (RSH): the dry heat the room itself picks up, after the supply-side allowances and the sensible safety margin. The dry heat of the fresh air is deliberately kept out of it — that is OA Sens.
RSH = ( Σ room sensible gains ) × (1 + (supply duct heat gain + supply duct leakage + fan heat) ÷ 100) × (1 + sensible safety ÷ 100)
Only the allowances whose tick box is on are counted, and percentages in the same bracket add together rather than compounding. See Supply gain and Sensible safety, whose default is a 10 % margin.
The gains that make up the sum. Six come through the envelope, three from inside the room, and a tenth, infiltration, only when the room carries an air-changes figure:
Qwall = U × Anet × Σn=0…23 cn × (Tsol-air, hour − n − Tindoor)
Qroof = U × Afloor × Σn=0…23 cn × (Tsol-air, hour − n − Tindoor) (top floor only)
Qglass, conduction = U × A × (Toutdoor, hour − Tindoor)
Qsolar = Awindow × [ Ebeam × sunlit fraction × SHGC(θ) + (Esky × sky view + Eground) × SHGCdiffuse ]
Qpartition = Σ (U × Agross) × (1 − partition reduction ÷ 100) × (Tout, month − Troom)
Qslab = U × Afloor × (1 − ground reduction ÷ 100) × (Tout, month − Troom) (ground floor only)
Qpeople = number of people × dry heat per person
Qlighting = lighting density × Afloor
Qequipment = equipment density × Afloor
Q = (1 − r) × q(h) + r × Σn RTFn × q(h − n)
Qinfiltration = (ACH × Afloor × Hceiling ÷ 3600) × ρ × cp × (Tout − Troom)
Where each input comes from. Wall U-values are the stamped copy of the wall's Exterior wall type from the Wall Presets; window U-values and SHGC start from the Window Presets and can be changed on the opening itself, on Window cards. A wall's face area is its length times the room's Ceiling height, and Anet takes the windows out of it. Roof U comes from the floor's Roof preset and the ground U is per floor, set as Floor U-value; partitions use the wall's Interior wall type and the two reductions are Partition ΔT and Ground ΔT. The wall's and roof's time factors and sol-air temperatures come from the preset's layers and absorptance, and the sun on each window from the station's clear sky, the preset's glazing type and its shading, as described under Walls and roof and Sun through windows; the basis is described on Calculation method. Dry heat per person is read off the industry-standard people-heat table for the room's Space type. The table is at 23.9 °C; at 26.7 °C the dry share drops a fifth and the moisture share rises by the same amount, so the figure is interpolated at the Indoor temperature between those two points, and multiplied by Occupants. The two densities default to 10 W/m² for Lighting load and 15 W/m² for Equipment load, each overridable per room. The air changes are the room's Infiltration figure, the room volume is its floor area times its Ceiling height, and the air density and specific heat are the same 1.2 kg/m³ and 1006 J/kg·K used for the fresh air under OA Sens.
The six envelope terms are taken at one moment. The application does not add each surface's own worst hour; it searches every month and every hour of the day — or the one month and hour you fixed under Calculation method — adds the six terms at that same moment, and keeps the largest sum. In cool months a conduction term can be negative and cancel part of the sun, which is allowed — the sum is what is maximised, not the parts. See How the worst hour is found.
A city with climate data is required. Without one, Calculate does not run; see Climate and site.
What is not in it. Air leaking in through the building fabric — infiltration — is counted only when the room carries an Infiltration figure; a blank field adds nothing, and no leakage is ever assumed from the construction or the openings. Doors carry no load: an exterior door's area stays in the wall face at the wall's U-value. The outdoor part of a partly exterior wall is charged as exterior wall; the rest counts as partition. Internal doors and windows are treated as part of the partition at the partition U-value, not as glass. Moisture gains are in Room Lat, and the fresh air is in OA Sens and OA Lat.
Reading the cell. Whole watts, no decimals. Zero for a NON-AC room. Summed across the floor on SUBTOTAL rows. Each gain listed above appears as its own line for one room under Sensible, and the step that applies the allowances and the margin opens the Coil list.
Room latent heat (RLH): the moisture load the room itself creates, after the supply-side allowance and the latent safety margin. The moisture the fresh air brings in is kept out of it — that is OA Lat.
RLH = ( number of people × moisture heat per person + Qinfiltration, latent ) × (1 + supply duct leakage ÷ 100) × (1 + latent safety ÷ 100)
Qinfiltration, latent = (ACH × Afloor × Hceiling ÷ 3600) × ρ × hfg × (wout − wroom)
People and infiltration are the only room moisture sources. The infiltration term is there only when the room carries an Infiltration figure, and uses the same outdoor and room moisture contents as the fresh air under OA Lat. Nothing else in the room contributes to this column: there is no allowance for cooking, for washing, for plants, for wet processes, or for moisture from equipment. A room with such a source is under-stated here, and the place to express it is the room's occupant count or its Space type.
Where the inputs come from. Moisture heat per person is read off the same table as the dry-heat figure, for the room's space type and interpolated at the Indoor temperature; the count is Occupants. Of the six allowances only Supply leak applies here, because leaking air carries moisture as well as heat, and the margin is Latent safety, whose default is a 5 % margin.
Reading the cell. Whole watts, no decimals. Zero for a room with no people and for a NON-AC room. Summed across the floor on SUBTOTAL rows. The people gain is a line under Latent, and the step that applies the allowance and the margin sits near the top of Coil.
The dry-heat load of the fresh outdoor air the room is given (OASH). It is reported apart from Room Sens because only part of it behaves like a room load.
Voa = rate per person × number of people + rate per area × Afloor
OASH = Voa × ρ × cp × (Tout − Troom)
The fresh-air quantity. The two rates are the standard outdoor-air rates for the room's space type, and either can be overridden per room with Ventilation per person and Ventilation per area. No further factor is applied: there is no diversity allowance, no efficiency correction and no percentage uplift on the quantity.
The temperatures. Tout is the design dry-bulb of the run's design case, which follows the station, the Design percentile and the Calculation method; Troom is the Indoor temperature. The difference is held at zero when outdoor air is the cooler of the two, so the column never goes negative and never credits the room for cool outdoor air. ρ follows the station's altitude.
Reading the cell. Whole watts, no decimals. Zero when the room needs no fresh air and for a NON-AC room. Summed across the floor on SUBTOTAL rows, and shown as its own step under Sensible.
The moisture load of the same fresh air (OALH): the heat needed to condense the extra water the outdoor air carries. It uses the same quantity as OA Sens.
OALH = Voa × ρ × hfg × (Wout − Wroom)
Where the moisture contents come from. Wout is worked out from the design case's dry-bulb and wet-bulb temperatures, and Wroom from the Indoor temperature and Indoor humidity. On the most humid design case this column is usually much larger than on the hottest one, which is why a room can be sized by a day that is not the hottest.
Reading the cell. Whole watts, no decimals. Held at zero when outdoor air is drier than the room, and zero for a NON-AC room. Summed across the floor on SUBTOTAL rows, and shown as its own step under Latent.
Effective room sensible heat: the room's own dry heat plus the share of the fresh-air dry heat that slips through the coil untreated. That share arrives in the room still at outdoor condition, so it behaves exactly like a room load.
ERSH = RSH + BF × OASH
BF is the Bypass factor, 0.10 by default and settable from 0.00 to 0.90. A higher bypass factor moves more of the fresh-air load into this column, which lowers Rise and so raises Supply air. ERSH is also the load the supply air has to carry, so it is the numerator in the Supply air formula.
Reading the cell. Whole watts, no decimals. Zero for a NON-AC room, summed across the floor on SUBTOTAL rows, and shown as its own step under Coil.
Effective room latent heat: the room's own moisture load plus the same bypassed share of the fresh-air moisture load. The construction is identical to ERSH.
ERLH = RLH + BF × OALH
Together with ERSH it sets ESHF, and their sum is the part of the coil duty that the room actually feels. Whole watts, no decimals, zero for a NON-AC room, and summed across the floor on SUBTOTAL rows.
Grand total heat (GTH): everything the coil has to remove for this room. It is the effective room load, plus the rest of the fresh-air load which goes straight to the coil, increased by the return-side allowances.
GTH = ( ERSH + ERLH + (1 − BF) × (OASH + OALH) ) × (1 + (return duct heat gain + return duct leakage) ÷ 100)
Again only ticked allowances count, and they add rather than compound; see Return gain and Return leak.
This is the column that decides things. Capacity and Intensity are both derived from it, and when both design cases are run it is the larger Grand Total that decides which run the whole row shows.
Reading the cell. Whole watts, no decimals. Zero for a NON-AC room. Summed across the floor on SUBTOTAL rows, and shown as its own step under Coil.
The room's cooling load expressed in the Cooling capacity unit. It is Grand Total converted straight to tons of refrigeration, with nothing added and nothing rounded away.
Capacity = GTH ÷ 3516.853
Nothing is rounded up to a machine size. A room working out at 2.024 tons is listed at 2.02 TR, and a room at 2.508 tons at 2.51 TR — the figure is the load itself, not a unit picked to cover it. Choosing the equipment, and any spare capacity that choice carries, is left to you. In SI the same figure is shown in kilowatts. See Cooling capacity.
On a SUBTOTAL row. The floor's figure is the sum of its rooms, which is also the floor's own Grand Total in tons — the two agree, because no room was rounded before being added in.
Zero for a NON-AC room, so such rooms never enter plant sizing. Shown to two decimals.
Grand Total divided by the room's floor area, in the Load intensity unit. It is the quickest way to compare rooms of different sizes.
Intensity = GTH ÷ Afloor
No value raises a flag: a high or low intensity is a result to read, not an error. A room with no area at all reports zero rather than dividing by zero.
Blank on SUBTOTAL rows: a floor-wide average would hide exactly the rooms that stand out. Shown to one decimal.
Effective sensible heat factor: the dry-heat share of the effective room load. It is a plain ratio with no unit, and it fixes the slope of the line the coil has to work along.
ESHF = ERSH ÷ (ERSH + ERLH)
A figure near 1.00 means a room whose load is almost all dry heat, and the coil can run warm; a lower figure means moisture dominates and the coil must run colder to wring the air out. It is what the apparatus dew point search aims at, alongside the room's own temperature and humidity.
When it is blank. If ERSH + ERLH comes out at zero or less — an empty room, or one whose envelope is a net loss — no coil is selected at all, and ESHF, ADP, Rise, Supply air, Supply, Entering and Leaving are all blank on that row. Blank on SUBTOTAL rows too, since averaging ratios would be meaningless. Shown to two decimals.
Apparatus dew point: the single surface temperature the coil is treated as having. There is no closed formula for it — it is found by searching down the saturation curve.
What the search is looking for. Picture the room condition as a point on a psychrometric chart. For any trial temperature T on the saturation curve, draw the line from the room point to that point and ask what share of the heat removed along it is dry heat:
slope(T) = cp × (Troom − T) ÷ ( cp × (Troom − T) + hfg × (Wroom − Wsaturated(T)) )
That share is 1.00 at the room's own dew point, where the line is horizontal and removes no moisture, and it falls as T drops. The ADP is the warmest temperature at which that share has fallen to the ESHF — the coil that removes heat and moisture in exactly the proportion the room needs.
How it is found. The search starts at the room's dew point and steps down in 0.25 K steps until the share first reaches or drops below the ESHF. That step and the one before it bracket the answer, and the bracket is then halved repeatedly until it is narrower than 0.01 K. The saturation curve itself is drawn for the station's barometric pressure, so a room at altitude gets a slightly different answer from the same room at sea level. When the ESHF is 1.00 there is no moisture to remove and the ADP is the room's dew point itself.
When it comes out blank. Two things can go wrong, and each also shows in the Flag column:
In both cases ADP, Rise, Supply air, Supply, Entering and Leaving are all blank on that row, while Room Sens through Capacity are still calculated and still valid. Shown to one decimal, and blank on SUBTOTAL rows. See Bypass factor.
When the config fixes it. With Fixed ADP ticked, this column shows the configured value on every row and the search only decides whether to flag the room ADP>REQUIRED. The column is then never blank.
How much colder than the room the supply air has to be, in the Temperature difference unit. It is not the full room-to-coil difference, because the bypassed air never reaches the coil temperature.
Rise = (1 − BF) × (Troom − ADP)
A larger rise means colder air and so less of it; raising the Bypass factor shrinks the rise and pushes the air quantity up. Blank whenever ADP is blank, and blank on SUBTOTAL rows. Shown to one decimal.
The air flow the room needs — the quantity that carries the effective room dry heat at the rise the coil can give. In the engine it is a volume flow in cubic metres per second, displayed in the Airflow unit.
V = ERSH ÷ ( ρ × cp × Rise )
What it is and is not. It is the dehumidified air quantity for this room alone, before any allowance for duct leakage as an air quantity — duct leakage is carried as a percentage on the loads, not as extra litres per second. If the room's fresh-air flow Voa comes out larger than this figure the room would have to run on outdoor air alone, and OA>SUPPLY is raised.
Blank when ADP is blank. Summed across the floor on SUBTOTAL rows, which gives the floor's total air quantity. Shown as a whole number.
Minimum airflow. A room with a Min airflow whose calculated figure falls short shows the minimum here instead, and is flagged MIN AIRFLOW. Rise, Supply, Entering and Leaving then follow from that larger flow.
The dry-bulb temperature of the air delivered into the room, in the Temperature unit. It is simply the room temperature less the rise.
Tsupply = Troom − Rise
This is the temperature at the diffuser as the calculation models it: the supply-side allowances are applied to the loads rather than as a temperature, so no fan or duct warming is added here. A very low figure is the usual sign of a room whose moisture load is forcing a cold coil. Blank whenever ADP is blank, blank on SUBTOTAL rows, and shown to one decimal.
The dry-bulb temperature of the mixed air arriving at the coil, in the Temperature unit. It mixes return air at room temperature with fresh air at outdoor temperature.
Tentering = Troom + ( Voa ÷ V ) × (Tout − Troom)
The fraction Voa ÷ V is the share of the supply air that is fresh, so the result slides between the room temperature at no fresh air and the outdoor temperature at all fresh air. Only dry bulb is reported — the moisture content of the mixture is not shown as a column. When the fraction is greater than 1 the mix is impossible and OA>SUPPLY is raised, but the number is still printed. Blank whenever ADP is blank, blank on SUBTOTAL rows, and shown to one decimal.
The dry-bulb temperature of the air coming off the coil, in the Temperature unit. It mixes air brought to the coil surface temperature with the share that bypassed it untouched.
Tleaving = ADP + BF × (Tentering − ADP)
At a bypass factor of zero this equals the ADP; at 0.10 it sits a tenth of the way back towards the entering temperature. It is the condition at the coil face only — supply fan heat and supply duct gain are carried as percentages on the loads, so they do not appear here, and Supply is not this figure. Blank whenever ADP is blank, blank on SUBTOTAL rows, and shown to one decimal.
Whatever the run has to say about the room, as text. At most three things are ever joined here, separated by a comma and a space.
The first is NON-AC when the room's Air-conditioned setting is No. The second is the coil result — REHEAT, FROST, OA>SUPPLY or ADP>REQUIRED. The third is MIN AIRFLOW when the room's minimum airflow set its supply air. A room can carry more than one, for example REHEAT, MIN AIRFLOW; a room with nothing to report has an empty cell.
STALE is different: it is not part of the result at all but a note that the room's inputs have been edited since the last Calculate, and while it applies it replaces the whole cell.
Blank on SUBTOTAL rows.
Which design day governed the room's shown result — the hottest-air day or the most-humid day. No formula: it names whichever of the two runs produced the larger Grand Total. For a zone, floor or building the same choice is made for the whole sum; see How zone, floor and building peaks are found.
The column shows one of four short codes:
| Code | Meaning |
|---|---|
peak_db |
The hottest day governs (both design days were run). |
peak_wb |
The most humid day governs (both design days were run). |
peak_db_only |
Only the hottest day was run ("Peak dry-bulb only"). |
fixed |
A fixed month and hour was calculated ("Specific month and hour"). |
Blank on SUBTOTAL rows. See Calculation method.
The room's Grand Total from the hottest-air design day's run, in the Heat load unit, whether or not that run governed. Only populated when both design cases were run.
Blank on SUBTOTAL rows and blank when the room was calculated against a single design case. See Calculation method.
The room's Grand Total from the most-humid design day's run, in the Heat load unit, whether or not that run governed. Only populated when both design cases were run.
Blank on SUBTOTAL rows and blank when the room was calculated against a single design case. See Calculation method.
Shown only after a run whose configuration has Calculate heating loads ticked. One row per room: first the room's own columns — Floor, Room Name, Room No., Zone (on the zone's color), Width, Depth and Area — then Heating load, Heating intensity, Humidification, Heating airflow and Heating flag. Every column is always shown; drag a column heading left or right to reorder them, and the order is remembered on this computer. Click a column heading to sort the rooms by it, inside their floor; click again to reverse the sort. The table is followed by a SUBTOTAL row per floor, a "floor × N storeys" row where a floor counts as several, one row per zone and a TOTAL row. All of these are plain sums: the winter design day is one steady moment, so there is no separate coincident peak for heating. The Floor and Zone filters above the tabs act on this table too: with a Floor or Zone filter set, the last row reads TOTAL (filtered) and covers only the rows shown. The room selected on the Cooling Load tab stays selected when you switch to this tab, and back again. Heating flag reads Airflow ↑ when the room needs more air at the heating supply temperature than its cooling fan delivers; Explain shows the supply temperature that would carry the heat at the cooling airflow. Double-click a room row to open Explain scrolled to its Heating group.

Cooling Load holds the table above; the filters and the gear sit above the tabs. Coincident peak, once a run used a city's weather data, reports the load with every room added at the same hour; it scrolls, so a tall building's floors and zones all reach the screen. Three figures come first: Sum of room peaks (each room at its own worst hour, the same total as the TOTAL row of an export), Coincident peak (the highest hour of the summed curve, with its month and hour), and the Difference between them. The figures cover the floors in the project, and the Coincident peak tile says how many those are. A storey you did not draw is counted through its typical floor's Counts as setting (see Floor settings); the tile then reads, for example, "15 storeys (3 drawn)". Floor rows and Single floor zones stay at one storey; a Multiple floors zone counts each of its floors once per storey. A table then lists Whole building first, then each zone, with the number of rooms each holds, in nine columns: name, Unit serves, Floors, Rooms, Sum of room peaks, Coincident peak, At, Sizing Case and Difference. A zone that is several identical units shows its size times the number of units, for example "12.4 TR × 3". A single-room row shows a dash for its difference. Below the table a Floors section, folded until you click its heading, holds one row per floor with the same columns.
The tab is cooling only. Heating has no coincident peak to find: the winter design condition is one steady moment with no sun and no internal gains, so every room meets it at once and the building's heating peak is the plain sum on the Heating Load tab.

Sizing Case names the design day that governs the row. With "Peak dry-bulb & wet-bulb" every row is added up twice, once with all its rooms under the hottest day and once with all of them under the most humid day, and the larger is shown; the two days are never mixed in one sum. Difference therefore covers rooms that peak at another hour and rooms that peak under the other design day. The steps, with a worked example, are in How zone, floor and building peaks are found.
A click selects the whole row. Double-click a row to see how its peak was added up. The panel that opens on the right is closed with Close Panel; while it is open, clicking another row shows that row instead. The panel names the design day that governs the row, and marks any room whose own peak came from the other one. The tab ends with how many rooms are still at Always 100%. The hour-by-hour figures behind the curve are written to the Excel report's Coincident Peak sheet. See Schedules.
The gear at the right-hand end of the results header, tooltip "Choose columns", opens a window that decides which of the columns above the table shows, in what order — the Excel export then writes exactly those columns in that order too.

| Field | What it does | Default | Read more |
|---|---|---|---|
| Available columns | Every column not currently shown. | — | Available columns |
| Columns shown | The columns the table shows, top to bottom in the order the table reads left to right. | The default columns and Flag | Columns shown |
| Save | Applies the choice and closes the window. | — | Save |
| Cancel | Closes the window without changing anything. | — | Cancel |
Everything not currently in Columns shown. Double-clicking an entry
here, or selecting one or more and pressing >, moves them into
Columns shown; >> moves every remaining one across at once.
The columns the table currently shows, listed top to bottom in the same
order the table reads left to right. Double-clicking an entry, or
selecting one or more and pressing <, sends them back to Available
columns; << drops everything and returns to the columns shown by
default — Floor, Room Name, Room No., Zone, Area, Occupancy, Lighting,
Equipment, Capacity, Supply air and Flag, in that order. All but Flag are
always in this list and cannot be sent back to Available columns,
though they can still be moved like any other entry; Flag can be sent
back. Until you change the columns, the table shows only these eleven.
A row can be dragged to a new position within this list, or moved with
the ↑ (Move up) and ↓ (Move down) buttons beside it; both act
on whatever is selected. Dragging a column heading left or right in the
results table itself reorders the same list, from the other end.
Applies the arrangement in Columns shown — what the table displays, what the Excel export writes, and the order of both — and closes the window. The choice is remembered on this computer for every project opened afterwards, not only the one open now.
Closes the window and throws away every change made since it was opened, leaving the table exactly as it was.
| Field | What it does | Default | Read more |
|---|---|---|---|
| SUBTOTAL | A shaded row per floor, summing its rooms. | — | SUBTOTAL |
Sums Area, Occupancy, Lighting, Equipment, Room Sens, Room Lat, OA Sens, OA Lat, ERSH, ERLH, Grand Total and Supply air across the floor's rooms, Capacity included — the rooms are unrounded, so their sum is the floor's own capacity. Room No., Zone, Width, Depth, Intensity, ESHF, ADP, Rise, Supply, Entering, Leaving, Flag, Sizing Case, Peak DB Total and Peak WB Total are left blank, and the row is not clickable.
| Field | What it does | Default | Read more |
|---|---|---|---|
| NON-AC | The room's Air-conditioned setting is No (filled from the name until set by hand). | — | NON-AC |
| STALE | The room's inputs changed after the last Calculate. | — | STALE |
| REHEAT | The coil selection found no apparatus dew point. | — | REHEAT |
| FROST | The apparatus dew point found is below freezing. | — | FROST |
| OA>SUPPLY | The fresh air alone exceeds the supply air needed. | — | OA>SUPPLY |
| ADP>REQUIRED | The fixed ADP is warmer than the room needs. | — | ADP>REQUIRED |
| MIN AIRFLOW | The room's minimum airflow set its supply air. | — | MIN AIRFLOW |
A room whose Air-conditioned setting is No is NON-AC. That setting starts from the room's name — toilet, WC, washroom, wash room, restroom, rest room, bathroom, bath room, ladies, gents, shaft, electrical, elec room, fire stair, stair, lift lobby, riser, duct or pipe shaft — until you pick a value yourself. Its Grand Total and Capacity are zero, so the room never enters plant sizing.
Set when a floor setting, an Update Floor, a re-read, or a preset change alters a room's inputs after it was last calculated. The row is shaded and the Flag cell reads STALE in place of any other flag, until the next Calculate clears it.
The apparatus-dew-point search found no point on the saturation curve at the load's required slope — the room's moisture load is too dominant for the coil alone, and reheat after the coil is needed.
The line to the saturation curve meets it only below freezing, so no coil alone can reach the point the room's load needs.
The room's fresh air is more than the supply air the coil selection calculated — the room would need to run on full outside air, with no return air at all.
Only with Fixed ADP ticked. The configured ADP is warmer than the one the search found for this room, or the search found none at all, so a coil at that temperature cannot remove enough moisture and the room would settle at a higher humidity than the indoor design. The air-side columns are still filled from the fixed value. Explain shows the required ADP beside the fixed one. This flag takes the place of OA>SUPPLY when both apply.
The room's Min airflow was more than the supply air the coil selection calculated, so Supply air shows the minimum and the air-side columns follow from it. Whether the extra air bypassed the coil or was reheated is the Min airflow setting of the run's configuration; Explain says which, and with reheat names the amount added to the Grand Total.
Click a row, or step through rows with the arrow keys, to select it; the whole row highlights, one row at a time. Clicking a row also zooms and centres the drawing on that room; selecting by arrow key moves only the table's highlight.
A SUBTOTAL row can be highlighted like any other row, but it has no room behind it — selecting one closes an explanation that was already open and leaves the drawing alone.
Selecting a row never opens the right-hand pane. Double-click a room row to open its full working there — see Explain — and only when the run used a city's weather data. While that pane is open, moving the selection to another room updates it to match; it closes when the SUBTOTAL row is selected, or when a filter change hides the room it was showing.
Clicking a room on the drawing selects its matching row in the table, unless the current floor or zone filter is hiding that room — the filter is never changed to reveal it.
The results pane only appears on the load calculation screen. Going Back keeps the results as they are; reopening the screen shows them again.